Chapter 4. Site Preparation for Octane

The Octane system is a powerful, graphics-intensive workstation, designed for the most complex of graphics tasks.

Octane systems are available with either single or dual MIPS processors.

Selecting a Location for an Octane System

Silicon Graphics Octane systems are designed to be located either on a desktop or beside a desk. Figure 4-1 shows an Octane system in a typical desktop configuration, and Figure 4-2 shows an Octane system in a typical deskside configuration.

Figure 4-1. Octane Typical Desktop Configuration

Octane Typical Desktop Configuration

Figure 4-2. Octane Typical Deskside Configuration

Octane Typical Deskside Configuration

Figure 4-3 shows the airflow path in Octane systems. The white arrows show the air intake areas on the top left, top right, top rear, and the front of the system. The darker arrow shows the air exhaust area at the rear of the system. Be sure that the location selected allows free flow of air to and from the areas shown.

Octane systems are designed for use in typical office computing environments: The air temperature should not fluctuate dramatically, air should circulate freely, and the location should be relatively dust free.

Figure 4-3. Octane Airflow

Octane Airflow

Octane Site Requirements

For information about selecting a physical location for an Octane system, see “Selecting a Location for an Octane System”.

Octane Specifications

Table 4-1 lists the physical specifications of the Octane chassis.

Table 4-1. Octane Chassis Physical Specifications

Dimensions

 

 

Installed:

length
width
height

16.2” (41.2 cm)
11.0” (28 cm)
16.3” (41.4 cm)

In Packaging[a]:

length
width
height

29.6” (75.2 cm)
21.3” (54.1 cm)
25.4” (64.5 cm)

Weight:

installed
in packaginga 

72 lbs (32.7 kg)
82 lbs (37.2 kg)

Air Temperature:

operating
in packaginga 

50° to 95° F (10° to 35° C)
14° to 149° F (-10\xβ0 to 65° C)

Thermal Gradient:

operating
in packaginga 

18° F (10° C) per hour (maximum)
108\xβ0 F (60° C) per hour (maximum)

Altitude:

operating
in packaginga 

10,000 ft (3,048 m) MSL (maximum)
40,000 ft (12,192 m) MSL (maximum)

Relative Humidity:

operating
in packaginga 

10-80% (non-condensing)
10-95% (non-condensing)

Vibration:

maximum

0.02”, 5-19Hz; 0.35 G, 19-500 Hz

[a] It is important that Octane systems be shipped only in their complete packaging, including the pallet.


Octane Power and Cooling Requirements

Table 4-2 provides power consumption and required cooling capacity information for the Octane system. For formulas, descriptions, and general information about power and cooling, refer to “ Electrical Requirements” in Chapter 2 and “ Thermal Requirements” in Chapter 2.


Caution: The power and cooling figures listed in Table 4-2 are maximums. Actual power and cooling requirements will vary, depending on configuration and load. Ask your SGI representative about particular configurations.


Table 4-2. Octane Power and Cooling Specifications

Volts:

 

100-120 volts AC, 1-phase
200-240 volts AC, 1-phase

Watts (from the wall):

maximum

850 watts (see “Caution,” above)

Power Factor:

minimum

0.98

Total Harmonic Dist.:

at 120 volts

5% maximum

Inrush Current:

peak

60 amps

Frequency:

 

47-63 Hz

Cooling Requirements:
(Also see “Caution” in
“Calculating Thermal Load” in Chapter 2)

maximum

2,899 Btu/hr (0.24-ton AC load) (see “Caution,” above)

Airflow Volume:

maximum

60 cfm (0.028 m3/s)

See Appendix B, “Site Power and Power Cables”, for information about Octane chassis site-wiring and power cables.

Octane External Peripherals

An Octane system typically has a one or more monitors, a keyboard, and a mouse. For more information, see “Monitors” in Appendix A, “Keyboards” in Appendix A, and “Mice” in Appendix A.

An Octane system may also have one or more external SCSI devices attached to it. For small SCSI devices, see “External SCSI Devices” in Appendix A. Also see information about Origin Vault systems in “Origin Vault Site Requirements” in Chapter 5.

Octane Cabling Issues

Besides power cables and external peripherals (mentioned above), Octane systems are typically wired to network cables, serial and parallel devices, and so on. For details of the ports found on an Octane workstation, see the Octane Workstation Owner's Guide.

See Appendix B, “Site Power and Power Cables”, for information about Octane chassis site-wiring and power cables.